Temperature setting range |
6 – 26 °C |
|
Response time (liquid element) |
~22 [Min] |
|
Hysteresis (liquid element)
|
0,6 [K]
|
|
Marking on temperature selector
|
0 - 5
|
|
Resolution
|
2 [°C]
|
|
Minimum setting of temperature selector
(Frost protection)
|
* (~6 [°C])
|
|
Locking device
|
at any position
|
|
Setting range restriction
|
minimum and maximun limitation available
contemporaneously
|
|
Maximum torsion to the temperature
selector
|
according to EN 215 part 1
|
|
Maximum load to the temperature selector
|
according to EN 215 part 1
|
|
Maximum ambient temperature
|
50 [°C]
|
|
Maximum working temperature
|
120 [°C]
|
|
Maximum permissible differential
pressure
|
1 [bar]
|
|
Maximum permissible static pressure
|
10 [bar]
|
|
Effect of water temperature
|
0,3 [K / 30K]
|
|
Differential pressure influence
|
0,15 [K]
|
|
flow rate at S1-1K |
90 [Kg / h]
|
|
Nominal flow rate
|
142 [Kg / h]
|
|
Characteristic flow rate at minimum
presetting of valve |
7 [Kg / h]
|
|
Characteristic flow rate at middle
presetting of valve |
76 [Kg / h]
|
|
Characteristic flow rate at minimum
setting of temperature selector |
140 [Kg / h]
|
|
Characteristic flow rate at maximum
setting of temperature selector |
148 [Kg / h]
|
|
Sensor Temperature correspond to
characteristic flow rate at minimum setting of temperature selector
|
6.3 [°C]
|
|
Sensor Temperature correspond to
characteristic flow rate at maximum setting of temperature selector
|
26.5 [°C]
|